Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1)

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 1
Series guide Valvepark Parts in Semiconductor Equipment
Part 1Chiller (you are reading this one)
Part 2Scrubber
Part 3CVD/ALD equipment
Part 4Etch equipment
Part 5Cleaning equipment
Part 6Vacuum equipment

At a Glance

Topic: The basic structure of a water-cooled chiller and its 4 ports

Structure: The circulating-fluid circuit and the refrigerant circuit meet at the evaporator, and cooling water carries away the heat from the condenser

Ports: Circulating-fluid supply and return, cooling-water inlet and outlet

Valve and strainer layout: A valve at all 4 ports, and a Y-strainer on the circulating-fluid return and the cooling-water inlet

Products covered: VP-01 2PC ball valve (BSPT, SS304, manual), PMV-15 3-way ball valve (BSPT, SS316, manual), GL11F-16P/R Y-strainer, H14W-16P/R swing check valve

A chiller is a unit that circulates fluid through process equipment to hold its temperature. A water-cooled chiller has two liquid paths. One is the circulating fluid, which picks up heat from the process equipment and returns to the chiller. The other is the cooling water, which carries the condenser heat to a cooling tower or similar. All 4 ports where these two liquids leave the chiller can be fitted with stainless steel valves, and a Y-strainer (a screen that filters out debris) can be added on the circulating-fluid return and the cooling-water inlet.

What Happens Inside a Chiller

The circulating-fluid circuit is the path where a circulation pump moves the fluid and a heat exchanger (the evaporator) cools it. A main tank, flow, pressure and temperature sensors, and a heater are sometimes added. The fluid can be water, a glycol solution, a fluorinated liquid (PFPE), and so on. The fluid returning from the process equipment gives up its heat at the evaporator.

The side that receives that heat is the refrigerant circuit, a vapor-compression refrigeration cycle made up of a compressor, condenser, expansion valve, and evaporator. The refrigerant absorbs heat from the circulating fluid at the evaporator, the compressor raises it to condensing pressure, and the condenser releases that heat outside. In a water-cooled unit, cooling water carries this heat away; in an air-cooled unit, the heat goes out into the air.

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 2

Inside the chiller: circulating-fluid circuit (orange), refrigerant circuit (dark gray), cooling-water circuit (blue-gray). All drawings are representative shapes, not the actual structure of any product.


Which Valves Are Used?

Four ports come out of a water-cooled chiller body: circulating-fluid supply and return, and cooling-water inlet and outlet. An air-cooled unit has no cooling-water ports, so its main ports are the 2 circulating-fluid ones.

A valve at all 4 ports, a Y-strainer only on the incoming side

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 3

Piping runs out of the chiller body, with a valve and a Y-strainer mounted on it.

The Y-strainer goes on the side flowing into the chiller, so debris carried in by the piping does not enter the chiller.

PortFlowValve and strainer layout
Circulating-fluid supplyChiller to process equipmentStainless steel valve
Circulating-fluid returnProcess equipment to chillerStainless steel valve, Y-strainer
Cooling-water inletFacility to chiller condenserStainless steel valve, Y-strainer
Cooling-water outletCondenser to facilityStainless steel valve

Circulating-fluid supply (chiller to process equipment): Stainless steel valve

Circulating-fluid return (process equipment to chiller): Stainless steel valve and Y-strainer

Cooling-water inlet (facility to chiller condenser): Stainless steel valve and Y-strainer

Cooling-water outlet (condenser to facility): Stainless steel valve

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 4

A manual ball valve (A) and a Y-strainer (B) on the piping.


Valves Already Inside the Chiller

A chiller has valves inside as well. The refrigerant circuit has an expansion valve, and some water-cooled models place a valve (such as a solenoid valve) on the condenser side to regulate cooling-water flow or to close when the compressor stops. Some models also have a check valve (a backflow-prevention valve) after the circulation pump, so check the chiller's internal configuration before adding a separate check valve to the external piping.


VP-01 2PC Ball Valve

The VP-01 is a 2PC ball valve that can be selected to match the threaded ports of a chiller.

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 5

VP-01 2PC ball valve (BSPT, SS304, manual)

ItemSpecification
Type2PC ball valve, manual (lever)
ConnectionBSPT, female thread on both ends
Body and ballSS304
SeatPTFE
Maximum working pressure1000 PSI
Size8A, 10A, 15A, 20A, 25A, 32A, 40A, 50A (1/4 in to 2 in)

Type: 2PC ball valve, manual (lever)

Connection: BSPT, female thread on both ends

Body and ball: SS304, seat: PTFE

Maximum working pressure: 1000 PSI

Size: 8A, 10A, 15A, 20A, 25A, 32A, 40A, 50A (1/4 in to 2 in)


3-Way Ball Valve: Where Cooling-Water Flow Is Split or Switched

Cooling-water piping does not always run as a single line. In some places one line must be split in two, or the flow must be switched to one of two lines. A 3-way ball valve changes the path with a single valve.

By the shape of the hole in the ball, 3-way valves divide into L-port and T-port. An L-port connects only two of the three ports, which suits switching to choose one path, while a T-port can connect all three at once, which suits splitting and merging. Choose the L-port for simple switching in the process sequence, and the T-port when several paths must be handled at the same time.

The PMV-15 is a manual 3-way ball valve used where cooling-water flow is split or switched.

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 6

PMV-15 3-way ball valve (BSPT, SS316, manual)

ItemSpecification
Type3-way ball valve, manual (lever), L-port and T-port
ConnectionBSPT, female thread
Body and ballSS316
SeatTFM1600
Maximum working pressure1000 PSI (1/4 in to 1-1/4 in), 800 PSI (1-1/2 in to 2 in)
Maximum working temperature180°C
Size8A, 10A, 15A, 20A, 25A, 32A, 40A, 50A (1/4 in to 2 in)

Type: 3-way ball valve, manual (lever), L-port and T-port

Connection: BSPT, female thread, body and ball: SS316, seat: TFM1600

Maximum working pressure: 1000 PSI (1/4 in to 1-1/4 in), 800 PSI (1-1/2 in to 2 in)

Maximum working temperature: 180°C

Size: 8A, 10A, 15A, 20A, 25A, 32A, 40A, 50A (1/4 in to 2 in)

The actuator mounting face follows the ISO5211 standard, so a pneumatic or electric actuator can be attached directly without a separate bracket even after the valve is installed as a manual one. The same 3-way family includes a bare version without actuator (PAV-07), pneumatic single-acting (PAVP-07(S)), pneumatic double-acting (PAVP-07(D)), and electric (PAVE-07). A pneumatic single-acting actuator returns to its home position by spring when the air is cut, while a double-acting one has no defined position when the air is cut.

Valvepark Recommended Setup

2PC ball valveVP-01
Threaded ports, selected to match the chiller port size
3-way ball valvePMV-15
Where cooling-water flow is split or switched

View product: 3-way ball valve BSPT (SS316, manual) PMV-15

If it is hard to decide which valve fits, please tell us your process environment and the parts you need. We will help you find a valve that matches your conditions.


GL11F-16P/R Y-Strainer: Where Debris Is Filtered Out

The threaded (female) Y-strainer GL11F-16P/R is fitted on the circulating-fluid return and the cooling-water inlet. If the chiller specification sheet sets a mesh size, match that value.

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 7

GL11F-16P/R Y-strainer

ItemSpecification
ModelGL11F-16P/R
TypeY-strainer
ConnectionThreaded (female)
Body and bonnetCF8/CF8M (stainless steel casting)
ScreenSS304/SS316
GasketPTFE
Size15A, 20A, 25A, 32A, 40A, 50A (1/2 in to 2 in)

Model: GL11F-16P/R

Type: Y-strainer, connection: threaded (female)

Body and bonnet: CF8/CF8M (stainless steel casting), screen: SS304/SS316

Gasket: PTFE

Size: 15A, 20A, 25A, 32A, 40A, 50A (1/2 in to 2 in)


H14W-16P/R Swing Check Valve: Where the Circulating Fluid Is Kept From Flowing Backward

When the circulation pump stops, the circulating fluid in the piping can flow backward. If the chiller has no internal check valve, a threaded (female) swing check valve H14W-16P/R on the external piping of the circulating-fluid supply side can prevent this.

Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1) photo 8

H14W-16P/R swing check valve

ItemSpecification
ModelH14W-16P/R
TypeSwing check valve
ConnectionThreaded (female)
Body, bonnet and discCF8/CF8M (stainless steel casting)
Screw and cylinder pinSS304
GasketPTFE
Size15A, 20A, 25A, 32A, 40A, 50A (1/2 in to 2 in)

Model: H14W-16P/R

Type: Swing check valve, connection: threaded (female)

Body, bonnet and disc: CF8/CF8M (stainless steel casting)

Screw and cylinder pin: SS304, gasket: PTFE

Size: 15A, 20A, 25A, 32A, 40A, 50A (1/2 in to 2 in)


Frequently Asked Questions Before Installation

Q. Won't a check valve cause water hammer?

A. It can. A check valve can worsen water hammer (a shock to the piping when the flow changes suddenly) when the pump stops, so a measure to reduce or relieve it should be decided together with the installation. The right measure depends on the piping layout and pump conditions, so if you tell us the circulation pump pressure and the pipe length, we will review the check valve selection with you.

Q. Which valve suits piping for a fluorinated circulating fluid?

A. A ball valve with a static seal structure is better than a plug valve. Some fluorinated liquids have low surface tension and seep through very small gaps, and in a plug valve such liquids mainly leak through the moving seal (the dynamic seal). Stainless steel 316 and PTFE generally resist fluorinated liquids well. Even so, seals and gaskets of the same material can lose plasticizer or swell depending on the compound, so it is best to test under actual conditions. The VP-01 body is SS304, so if the circulating fluid calls for more corrosion resistance, an SS316 specification is reviewed separately. For valve selection, tell us the operating temperature and the type of circulating fluid, and we will match it to the specification.

Q. The chiller port is a tapered female thread (such as Rc). Can I fit a female-thread valve?

A. Not directly; a fitting is needed. To connect a female-thread valve to a female-thread port, join them with a fitting such as a nipple that has male threads on both ends, and the VP-01, which is female on both ends, is connected the same way.


Information to Prepare for a Quote Request

Tell us your process environment and the parts you need, and we will advise you. It is fine if some items are not decided yet.

1. Fluid and temperature: type of circulating fluid, set temperature range

2. Parts needed: type and quantity of valves, strainers, or check valves

3. When you need them

At the Valvepark shop you can find products by size, material, and pressure, check the specifications, and order right away on PC or mobile.

If you need a quotation, a test certificate, or a tax invoice, please contact us at the address below.

Next part Basic Scrubber Structure and Where Valves Go in Water Piping: What to Fit Where (Valvepark Parts in Semiconductor Equipment, Part 2)

Purchase and Inquiries

Valvepark Official Contact

Buying piping materials, made easy and fast.

Emailsales@valvepark.com
Phone1666-0215
KakaoTalk channelGo to KakaoTalk chat
WebsiteGo to the Valvepark website
Product pageView VP-01 2PC ball valve
Smart StoreGo to the Valvepark Smart Store
Basic Chiller Structure and Its 4 Ports: Which Valves and Strainers Are Used? (Valvepark Parts in Semiconductor Equipment, Part 1)