HK1 is a 2-position gas shut off valve with an integrated motor and hydraulic pump, for main gas lines. It is NC type (open when energized) for city gas, natural gas and LPG. Ports are Rp1 1/2, Rp2 and Rp2 1/2 (screw-in), 40A to 80A (JIS flange) and 100A to 200A (DIN flange). A flow rate controller and strainer are provided (no flow rate controller for 125A to 200A).


| Working Fluid | City gas / natural gas / LPG |
| Valve Structure | Fluid operated 2-position shut off valve (integrated motor/hydraulic pump), NC (open when energized) |
| Working Pressure | HK1-40/40J: 0 to 0.4 MPa / -50/50J: 0 to 0.25 MPa / -65/65J: 0 to 0.2 MPa / -80J: 0 to 0.14 MPa / -V100F: 0 to 0.1 MPa / -V125F: 0 to 0.06 MPa / -V150F: 0 to 0.04 MPa / -V200F: 0 to 0.023 MPa |
| Flow Rate (natural gas specific gravity 0.65, ΔP = 0.25 kPa, m³/h (ANR)) | -40: 59 / -50: 96 / -65: 145 / -80J: 196 / -V100F: 287 / -V125F: 399 / -V150F: 601 / -V200F: 950 |
| Cv | -40: 39 / -50: 64 / -65: 97 / -80J: 132 / -V100F: 191 / -V125F: 265 / -V150F: 399 / -V200F: 631 |
| Flow Rate Conversion Coefficient (multiply flow rate in table) | Natural gas (13A) 1.0, city gas (6B/6C) 1.09, propane 0.63, butane 0.57, butane-air (6A) 0.72 |
| Rated Voltage | 100 VAC ±10%, 200 VAC ±10% (common to 50 and 60 Hz) |
| Power Consumption (apparent power) | When opening 120 VA (100 VAC) / 115 VA (200 VAC), when held open 12 VA |
| Ambient Temperature | -15 to 60 °C (no freezing) |
| Opening Time / Closing Time | 30 s or less (ambient temperature 0 to 60 °C, rated voltage) / 1.0 s or less |
| Frequency | 4 cycles/min. or less |
| Flow Rate Adjustment | 0 to 100% (no flow rate controller on -V125F, -V150F and -V200F) |
| Mounting Orientation | Vertical direction with the actuator up or horizontal direction with the terminal box side of actuator up |
| Connection / Port Size | -40: Rp1 1/2 (screw-in) / -40J: 40A (JIS10KRF) / -50: Rp2 / -50J: 50A / -65: Rp2 1/2 / -65J: 65A / -80J: 80A / -V100F: 100A / -V125F: 125A / -V150F: 150A / -V200F: 200A (DIN PN16) |
| Weight | -40: 9 kg / -40J: 21.5 / -50: 9.2 / -50J: 10.7 / -65: 12.7 / -65J: 14.3 / -80J: 15.3 / -V100F: 19 / -V125F: 24 / -V150F: 32 / -V200F: 52 kg |
| Proof Pressure | Up to -80J: 0.6 MPa / -V100F: 0.2 / -V125F: 0.12 / -V150F: 0.08 / -V200F: 0.05 MPa |
| Degree of Protection | IP54 (IP21 equivalent with HP terminal box) |