CKD VNA Gas Shut Off Valve (Quick Open, Rp1/2 to Rp2 1/2)

VNA is a quick open gas shut off valve for low pressure up to intermediate pressure (45 kPa). It is NC type (open when energized) for city gas, natural gas and LPG. Nine port sizes from Rp1/2 to Rp2 1/2 are available, and the flow rate (calorie) can be adjusted even after installation.

CKD VNA Gas Shut Off Valve (Quick Open, Rp1/2 to Rp2 1/2)CKD VNA Gas Shut Off Valve (Quick Open, Rp1/2 to Rp2 1/2) 2

Specifications

Working FluidCity gas / natural gas / LPG
ActuationNC (open when energized), quick open
Working PressureVNA-15: 0 to 45 kPa / VNA-20 to 40: 0 to 30 kPa / VNA-50 and 65: 0 to 20 kPa / VNA-32-D and 40-D: 0 to 5 kPa
Flow Rate (natural gas specific gravity 0.65, ΔP = 0.25 kPa, m³/h (ANR))-15: 6.9 / -20: 14.8 / -25: 18.7 / -32: 30.3 / -40: 34.5 / -50: 70.0 / -65: 112.6 / -32-D: 45.0 / -40-D: 49.0
Cv-15: 4.6 / -20: 9.9 / -25: 12.5 / -32: 20.4 / -40: 23.2 / -50: 47.1 / -65: 75.8 / -32-D: 30.3 / -40-D: 33.0
Flow Rate Conversion Coefficient (multiply flow rate in table)Natural gas (13A) 1.0, city gas (6B/6C) 1.09, propane 0.63, butane 0.57, butane-air (6A) 0.72
Rated Voltage100 VAC (+10/-15%), 200 VAC (+10/-15%) (common to 50 and 60 Hz)
Power Consumption (apparent power)VNA-15, 20 and 25: 31 VA / VNA-32 and 40: 50 VA / VNA-50: 73 VA / VNA-65: 74 VA / VNA-32-D and 40-D: 50 VA
Ambient Temperature-20 to 60 °C (no freezing)
Opening Time / Closing Time0.5 s or less / 1.0 s or less
Frequency30 cycles/min. or less
Flow Rate Adjustment20 to 100% (not applicable to VNA-32-D and 40-D)
Mounting OrientationVertical direction with the coil on top or horizontal direction with the coil horizontal
Connection / Port SizeScrew-in (Rp) / -15: Rp1/2, -20: Rp3/4, -25: Rp1, -32: Rp1 1/4, -40: Rp1 1/2, -50: Rp2, -65: Rp2 1/2, -32-D: Rp1 1/4, -40-D: Rp1 1/2
Weight-15: 1.7 kg / -20: 2.5 / -25: 2.4 / -32: 4.0 / -40: 3.9 / -50: 8.3 / -65: 14.6 / -32-D: 3.7 / -40-D: 3.7 kg
Proof Pressure0.1 MPa
Degree of ProtectionIPX4