Products: VALVEPARK temperature regulators TR01 (for heating) and TR02 (for cooling)
Operation: self-acting, expansion principle, no external power required
Controlled variable: fluid temperature (set temperature up to 250°C)
Specifications: 1/2"~6" (15A~150A), flange, ASME Class 150~300 (PN16~40)
Domestic hot water systems, storage tanks and district heating heat exchanger stations all have points where the fluid temperature must be held at a set value. The VALVEPARK TR01 and TR02 are self-acting temperature regulators whose valves open and close on changes detected by a temperature sensor, and they need no electricity or compressed air. The TR01, which closes as the temperature rises, is used for heating control, and the TR02, which opens, is used for cooling control.
Closing type for heating control, opening type for cooling control
In a system that heats a fluid such as hot water with a heat exchanger, the amount of heat delivered depends on the flow rate of the heating medium, so too much or too little flow moves the hot water temperature away from the set value. The temperature regulator uses a valve to increase and decrease this flow and bring the temperature back toward the set value.
The temperature regulator consists of a globe valve, a thermostat that includes a set point adjuster, a capillary tube and a temperature sensor, and it works on the expansion principle. The temperature change detected by the sensor is carried through the capillary tube to the valve, and that force changes the plug position. The desired temperature is set with the set point adjuster on the thermostat.
On the heating side, the valve is installed in the pipeline through which the heating medium enters the heat exchanger, and the sensor is connected by the capillary tube so that it detects the temperature on the heat exchanger side. It is designed for a wide range of industrial heating and cooling control and suits the hot water systems, storage tanks and district heating heat exchanger stations mentioned above. The TR02 for cooling control is applied to the same heat exchanger piping layout.
The TR01 and TR02 are two models of the Temperature Regulator product line.
TR01 temperature regulator (closes as temperature rises)
TR02 temperature regulator (opens as temperature rises)
| Model | Action | Control purpose |
|---|---|---|
| TR01 temperature regulator | Closes as temperature rises | Heating control |
| TR02 temperature regulator | Opens as temperature rises | Cooling control |
In the heat exchanger layout above, the TR01 senses the hot water side temperature with its sensor. When the temperature exceeds the set value, the valve closes and the flow of the heating medium falls, and when the temperature drops, the valve opens again. In cooling control the TR02 moves the other way: as the temperature rises the valve opens and the flow on the cooling side increases.
However, a self-acting regulator may not suit a process where the set temperature is changed often or where a narrow deviation around the set value must be held, so check the control conditions first.
| Item | TR01 and TR02 (common) |
|---|---|
| Size | 1/2"~6" (15A~150A) |
| Connection | Flange |
| Pressure class | ASME Class 150~300 (PN16~40) |
| Set temperature | Up to 250°C |
| Body material | Carbon steel, stainless steel, alloy steel, duplex stainless steel |
| Plug material | SS304, SS316, FKM, PTFE, PPL |
| Bellows material | Stainless steel |
| Options | Thermostat T06/T17, capillary tube, temperature sensor, immersion pocket |
The fluid temperature that can actually be used depends on the seal type, the size and whether a stem extension is applied.
| Allowable operating temperature | 15~125A | 150A |
|---|---|---|
| Hard seal | 150°C or below | 140°C or below |
| Hard seal + stem extension | 250°C or below | Inquire |
| Soft seal | 100°C or below | 100°C or below |
The allowable differential pressure (the pressure difference that can be applied across the valve) decreases as the size increases, so for large bores check the operating differential pressure first.
| Allowable differential pressure (MPa) | 15~80A | 100~125A | 150A |
|---|---|---|---|
| PN16 | 1.6 | 1.5 | 1.2 |
| PN40 | 2.0 | 1.5 | 1.2 |
| Size | L | B | Weight (kg) |
|---|---|---|---|
| 15A | 130 | 212 | 6.2 |
| 20A | 150 | 212 | 6.7 |
| 25A | 160 | 238 | 9.7 |
| 32A | 180 | 238 | 13.0 |
| 40A | 200 | 240 | 14.0 |
| 50A | 230 | 240 | 17.0 |
| 65A | 290 | 275 | 29.0 |
| 80A | 310 | 275 | 33.0 |
| 100A | 350 | 380 | 60.0 |
| 125A | 400 | 380 | 70.0 |
| 150A | 480 | 295 | 80.0 |
| Model | l | D | R | m | Weight (kg) |
|---|---|---|---|---|---|
| T06 | 380 | 24 | 1" | 280 | 3.0 |
| T17 | 500 | 30 | 1" | 280 | 3.5 |
Unit: mm (R in inches), tolerance ±0.5 mm
Q. Can it be used with 250°C fluid?
A. For sizes 15~125A, applying a valve stem extension allows use up to 250°C. A hard seal without the extension is rated for 150°C or below, and a soft seal for 100°C or below. A 150A hard seal is rated for 140°C or below.
Q. What happens if the power or compressed air is cut off?
A. The control action has nothing to do with the supply of power or compressed air. It works on the temperature change of the controlled fluid, and the temperature sensor and capillary tube carry that signal to the valve, so no separate supply system is needed.
Q. Can it replace an existing temperature regulator in the same position?
A. Replacement can be considered when the size and pressure class are the same, the connection is a flange and the L value in the dimension table matches. The set temperature and the thermostat (T06, T17) size are checked separately.
1. Model: TR01 (heating control) or TR02 (cooling control)
2. Size and pressure class: bore (A), flange connection, ASME Class 150 or 300
3. Operating conditions: set temperature, fluid type and operating temperature (whether a stem extension is needed), operating differential pressure
4. Options: thermostat T06 or T17, capillary tube, temperature sensor, immersion pocket
Other models in the same regulator line are introduced by purpose: PRR01 and PRR02 for pipeline pressure control, PDRC01 and PDRO01 for differential pressure control, and MPR01 and MPR02 for tank micro-pressure control.
Purchase and Inquiries
| sales@valvepark.com | |
| Phone | 1666-0215 |
| KakaoTalk Channel | Chat on KakaoTalk |
| Website | Go to the VALVEPARK website |
| Smart Store | Go to the VALVEPARK Smart Store |